Amistad Home Page
     

AMISTAD'S INTEGRATED STRONG ARM (CAI UNIT) TECHNICAL SHEET - DECEMBER 31, 2002
Material - Complete composite integrated unit with replaceable insulator/pin components
Approximate weight 44 lbs
Voltage coverage 12kv to 35kv
Phase distances outside to outside 60.5"
  top phase to outside phase 34"

BIL lightning disruptive discharge voltage test (positive) 545kv
  lightning disruptive discharge voltage test (negative) 624kv

RIV (radio interferance) at 850 kHz ,10uv negative
PD
  negative

Dry flashover
60Hz 317kv average phase to phase
  60Hz
229kv average phase to bolt
Wet flashover
60Hz
140kv average phase to bolt

Power frequency withstand voltage test, with clean fog on clean crossarm 38.5kv
withstood - noflashover
Power frequency limit voltage test, with clean fog on clean crossarm. 38.5kv withstood - noflashover
Power frequency withstand voltage test, with clean fog on contaminated crossarm (solid layer) at 38.5kv
withstood - noflashover

Accelerated Heavy Fog Aging Chamber 1002 with no flashovers and minimal track marks
Accelerated Aging UV Weather Ometer Exposure per ASTM G155-00 1000 hours - slight discoloration, no
apparent damage to coating or substrate
Accelerated contamination aging completed soon

Down loading - Sgt Outboard phase 4000 lbs no evidence of arm failure - required 3000 lbs.
  - Two Outboard phases 12,160 lbs no evidence of arm failure - required 6000 lbs.
Longitudinal Load - Sgt Outboard phase 430 lbs no evidence of arm failure - bolt bending
Transverse - Sgt outboard phase 4920 lbs. no evidence of arm failure - required 3000 lbs.
Transverse - Outboard pin 1170 lbs no evidence of failure - required load of 1000 lbs
Transverse - Center pin 1180 lbs. no evidence of failure - required load of 1000 lbs
Longitudinal - Center pin 1110 lbs. no evidence of failure of pin at required load of 1000 lbs
Wet & Dry Flashover test session on 10-29-01 at NeeTrac Lab, Atlanta GA
phase to phase dry flashover test phase to bolt dry flashover test
average results, 317,000 volts average results, 229,000 volts
Balance of Electrical and aging testing conducted at Swedish Transmission Research Institute (STRI) in Ludvika, Sweden
Heavy Fog Test Lightning Impulse (BIL) test
11-22-01 at STRI Labs, Ludsvika, Sweden 11-19-01 at STRI Labs, Ludsvika, Sweden
Accelerated Weather Exposure UV test at SP Swedish National Testing and Research Institute in Boras, Sweden

©2002 HOME | CAI UNIT | OTHER PRODUCTS | ORDER INFO | CONTACTS